NTSB released a report about the fire onboard the vehicle carrier Alliance St. Louis. The vehicle carrier Alliance St. Louis was under way from Port Arthur, Texas, to Jacksonville, Florida, when a pipe plug on the fuel pump for the main engine’s no. 6 cylinder came loose, resulting in fuel spray onto the engine’s hot exhaust gas pipe manifold. The atomized fuel quickly ignited. The fire was contained to the main engine room and extinguished by the CO2 fixed fire-suppression system. No injuries were reported; property damage exceeded $3,750,000.
Summary:
About 1500, the second assistant engineer on duty set the engine room to unmanned mode, as was typically done at the end of each work day. The second assistant engineer conducted a routine round of the engine room at 2200 and again at 2300 before going to bed. This was the last time the crew entered the engine room that night. The second assistant engineer told investigators that he did not see or hear anything unusual in the main engine, and no alarms were recorded that evening in the alarm history log in the control room.
Early in the morning on January 16, the main engine’s low fuel oil inlet pressure alarm sounded, the engine room general alarm activated on the bridge and in the engineering officers’ staterooms and the vessel’s fire-detection system activated. Seconds later, the ship lost main electrical services, including power to the main propulsion and steering systems. The emergency diesel generator automatically started and came online as designed, providing power to essential equipment and the steering system.
The pipe plug was likely not sufficiently torqued into the top cover during the last inspection because the crew did not recognize this as a crucial step in maintaining the reliability of the fuel oil system. The instruction book’s section Overhaul of Top Cover Complete contributed to the crew’s lack of awareness, because it did not depict the fuel oil return passages or describe the purpose of the pipe plugs.
The last step of the top cover overhaul procedures stated, “mount the protective cap (spray shield) over the puncture valve, three drain oil pipes, return oil pipe, air pipe and safety system on the top cover.” There were openings for screwing spray shields to the top covers. However, none of the ship’s spray shields were screwed to their top cover. The spray shield on the no. 6 cylinder’s top cover was found hanging off the air pipe next to the pump housing during the post-accident inspection. It was likely knocked off the top cover by the pipe plug and spraying MGO because it was not properly secured with two screws.
A properly secured spray shield (per the manufacturer’s instruction manual) would have kept the MGO from spraying directly into the air and contacting the no. 6 cylinder exhaust gas pipe/receiver. Instead, the MGO would have sprayed into the shield and run down the fuel pump housing to the decks below where there were fewer, if any, potential sources of ignition.
Investigators found gaps in the lagging (insulation) and steel plating at every cylinder’s exhaust gas pipe/manifold interface. At the no. 6 exhaust gas manifold, the gap was approximately half an inch around most of the exhaust pipe where it joined to the manifold.
Based on fire damage, flames and intense heat burned the overhead above the no. 6 cylinder. From there, flames, smoke, and hot gas spread horizontally in all directions toward the bulkheads. The crew’s timely and effective use of the CO2 fixed fire-suppression system likely prevented the spread of the fire and minimized the extent of damage to the engine space.
Early on January 16, the Alliance St. Louis’s main engine’s low fuel oil inlet pressure alarm sounded. Shortly after, the engine room alarm activated on the bridge and in the engineering officers’ staterooms, followed by the vessel’s fire-detection system. Moments later, the ship lost power to the main propulsion and steering systems. The emergency diesel generator automatically started and came online, providing power to essential equipment and the steering system.
The bridge crew activated the general alarm on the bridge and crewmembers reported to their emergency stations. The chief mate and the chief engineer went to investigate the spaces that the problem was reported in, while two fire teams prepared the firefighting gear. The chief mate saw thick black smoke exiting from the ventilation louvres filling with smoke. The crewmembers then closed the engine room ventilation dampers and control stops to prevent the spread of smoke and reduce the supply of oxygen. They also shut the fuel and lube oil quick-closing valves to cut off potential fuel sources to the fire.
The master decided to extinguish the fire using the engine room’s CO2 firefighting equipment. The crew released CO2 into the engine room, each time accounting for all persons ahead of time. After the third release, the engine room temperatures decreased and then stabilized.
The crew’s timely and effective use of the CO2 firefighting equipment lprevented the spread of the fire and minimized the extent of damage to the engine space.
The pipe plug was probably not torqued enough into the top cover during the last inspection because the crew did not recognize this as a crucial step in maintaining the reliability of the fuel oil system. The instruction book’s section Overhaul of Top Cover Complete played a role to the crew’s lack of awareness about this dangerous situation because it did not depict the fuel oil return passages or describe the purpose of the pipe plugs.
Probable Cause:
The National Transportation Safety Board determines that the probable cause of the engine room fire aboard the Alliance St. Louis was improper tightening of a pipe plug on the top cover of the no. 6 cylinder fuel pump housing, which resulted in a high-pressure release of marine gas oil. Contributing to the fire was the improper attachment of a fuel spray shield to the top cover, which allowed fuel to spray directly onto the cylinder’s hot exhaust pipe and ignite.
Did you subscribe for our daily newsletter?
It’s Free! Click here to Subscribe!
Source: NTSB
DASPOS A/S and DASPOS USA, Inc. Is specialized in fire prevention. The LAS-10 is an atmospheric oil mist and gas leakage detection system, designed to analayze large volumes of air (10.000 Ltr/Min) and detect any leakages from MGO / HFO / Hydraulics etc. The system is designed to warn the crew and operators ahead of a potential escalation. The LAS-10 detectors are type approved by Classification and complies with all regulations. Check our website for http://www.daspos.com