Lessons Learned: Battery Explosion During Routine Maintenance

603

IMCA, in its Safety Events, reports of a battery explosion during routine maintenance.

What happened

A chief engineer suffered minor injuries in a battery explosion when disconnecting a cable from the battery. The incident occurred onboard a harbour tug. The chief engineer was planning to replace a battery disconnect switch that had failed. While disconnecting the positive terminal, both terminals were inadvertently short-circuited with a spanner and the battery exploded causing injuries to the chief engineer. Operations were stopped, first aid was given, and the tug returned alongside. After assessment at hospital the chief engineer returned to the tug with only minor injuries. The tug was out of service for four hours.

What went right?

  • The external power supply breaker was switched off.
  • To be able to work on the switch safely, it was decided to disconnect the battery cables so the switch would be isolated from the battery 24VDC.

What went wrong

The battery was inadvertently short-circuited with a spanner.

Lessons learned

Protect battery terminals with plastic caps to avoid accidental contact.

Ensure proper PPE (gloves, apron, face shield) is used when working on batteries.

Consider the use of tools appropriate for battery handling.

Changes to vessel planned maintenance system:

  • Follow manufacturers recommendations for battery maintenance
  • Increase the frequency of battery maintenance inspection to gain better control of batteries in a poor state.
  • Consider the installation of battery chargers with temperature sensors.