Lesson Learned: Person Crushed in Watertight Door

301

IMCA, in its Safety Events, reports an incident where a crew person was crushed in a watertight door.

What happened

An electrician was crushed and severely injured while working on a watertight door on a vessel. He was evacuated by helicopter. The incident happened when the door opened unexpectedly, during the adjustment of a proximity sensor for the door.

Just before this adjustment, the electrician had closed a ball valve in the hydraulic system, believing this was a safety valve that would prevent the door from opening. Once working on the system, the selector switch on the primary operating system, which is used to open and close the watertight door, did not return to the neutral position enabling a signal to be sent to the PLC (programmable logic controller).

When the electrician manually aligned the sensor which he had to repair, a signal went to the PLC and the door opened unexpectedly crushing him between the door and the deck.

What went wrong

  • The system was not isolated at the time of the incident – no Lock-out/Tag-out of the system was in place;
  • There was no request for a Permit To Work (PTW) nor was a Job Safety Analysis (JSA) prepared for the activity;
  • The ball valve did not isolate the hydraulic system:
    • The ball valve was not a safety valve;
    • The ball valve was leaking.
  • The door opened when the command “open” came in from the PLC. This command came in because the selector switch was damaged and did not return to the neutral position once released;
  • When the door is operated, visual and audible alarms are initiated. The alarms and signals were not fully operational or working.

Lessons learned

  • Ensure there is a Permit To Work in place, a Lock-out/Tag-out procedure, and a suitable and sufficient job safety analysis before you start;
  • Hydraulic system ball valves are not “safety valves”. Take care that you fully understand what you’re working on, and ensure systems are fully de-energizing before putting yourself in the line of fire;
  • The switch on the primary operating system was not in working condition but there were not sufficient spares on board to replace them. Sufficient spare parts should be on board, so these can be replaced immediately.

Did you subscribe to our daily Newsletter?

It’s Free! Click here to Subscribe

Source: IMCA

4 COMMENTS

  1. Right here is the right blog for anyone who wants to understand this topic.

    You know a whole lot its almost tough to argue with you (not that I actually would want to…HaHa).
    You certainly put a brand new spin on a topic that’s been discussed for many years.

    Excellent stuff, just excellent! I saw similar here: Sklep internetowy

  2. I’m not that much of a online reader to be honest but your sites
    really nice, keep it up! I’ll go ahead and bookmark your
    site to come back in the future. Cheers I saw similar here: Najlepszy sklep

  3. Wow, fantastic blog layout! How long have you been running a blog
    for? you made running a blog glance easy. The whole look of your site is great,
    as neatly as the content material! You can see similar:
    najlepszy sklep and here sklep internetowy

Comments are closed.